Corona Effect in Power System
Electric power transmission practically deals in the bulk transfer of electrical energy, from generating stations situated many kilometers away from the main consumption centers or the cities. For this reason the long distance transmission cables are of utmost necessity for effective power transfer, which in-evidently results in huge losses across the system. Minimizing those has been a major challenge for power engineers of late and to do that one should have a clear understanding of the type and nature of losses. One of them being the corona effect in power system, which has a predominant role in reducing the efficiency of EHV(extra high voltage lines) which we are going to concentrate on, in this article.What is Corona Effect in Power System and Why it Occurs?
For corona effect to occur effectively, two factors here are of prime importance as mentioned below:- 1) Alternating electrical potential difference must be supplied across the line. 2) The spacing of the conductors, must be large enough compared to the line diameter. When an alternating current is made to flow across two conductors of the transmission line whose spacing is large compared to their diameters, then air surrounding the conductors (composed of ions) is subjected to di-electric stress. At low values of supply end voltage, nothing really occurs as the stress is too less to ionize the air outside. But when the potential difference is made to increase beyond some threshold value of around 30 kV known as the critical disruptive voltage, then the field strength increases and then the air surrounding it experiences stress high enough to be dissociated into ions making the atmosphere conducting. This results in electric discharge around the conductors due to the flow of these ions, giving rise to a faint luminescent glow, along with the hissing sound accompanied by the liberation of ozone, which is readily identified due to its characteristic odor. This phenomena of electrical discharge occurring in transmission line for high values of voltage is known as the corona effect in power system. If the voltage across the lines is still increased the glow becomes more and more intense along with hissing noise, inducing very high power loss into the system which must be accounted for.Factors Affecting Corona Effect in Power System.
As mentioned earlier, the line voltage of the conductor is the main determining factor for corona in transmission lines, at low values of voltage (lesser than critical disruptive voltage) the stress on the air is too less to dissociate them, and hence no electrical discharge occurs. Since with increasing voltage corona effect in a transmission line occurs due to the ionization of atmospheric air surrounding the cables, it is mainly affected by the conditions of the cable as well as the physical state of the atmosphere. Let us look into these criterion now with greater details :Atmospheric Conditions for Corona in Transmission Lines
It has been physically proven that the voltage gradient for di-electric breakdown of air is directly proportional to the density of air. Hence in a stormy day, due to continuous air flow the number of ions present surrounding the conductor is far more than normal, and hence its more likely to have electrical discharge in transmission lines on such a day, compared to a day with fairly clear weather. The system has to designed taking those extreme situations into consideration.Condition of Cables for Corona in Transmission Line.
This particular phenomena depends highly on the conductors and its physical condition. It has an inverse proportionality relationship with the diameter of the conductors. i.e. with the increase in diameter, the effect of corona in power system reduces considerably. Also the presence of dirt or roughness of the conductor reduces the critical breakdown voltage, making the conductors more prone to corona losses. Hence in most cities and industrial areas having high pollution, this factor is of reasonable importance to counter the ill effects it has on the system.Spacing between Conductors
As already mentioned, for corona to occur effectively the spacing between the lines should be much higher compared to its diameter, but if the length is increased beyond a certain limit, the di-electric stress on the air reduces and consequently the effect of corona reduces as well. If the spacing is made too large then corona for that region of the transmission line might not occur at all.Power loss due to corona
Formation of corona is always accompanied by energy loss
which is dissipated in the form of light, heat, sound and chemical action. When disruptive voltage is
exceeded, the power loss due to corona is given by :